Age | Commit message (Collapse) | Author | Files | Lines | |
---|---|---|---|---|---|
2022-04-27 | hwmon: (pmbus) delta-ahe50dc-fan: work around hardware quirk | Zev Weiss | 1 | -0/+16 | |
CLEAR_FAULTS commands can apparently sometimes trigger catastrophic power output glitches on the ahe-50dc, so block them from being sent at all. Signed-off-by: Zev Weiss <zev@bewilderbeest.net> Cc: stable@vger.kernel.org Link: https://lore.kernel.org/r/20220427035109.3819-1-zev@bewilderbeest.net Fixes: d387d88ed045 ("hwmon: (pmbus) Add Delta AHE-50DC fan control module driver") Signed-off-by: Guenter Roeck <linux@roeck-us.net> | |||||
2021-12-26 | hwmon: (pmbus) Add Delta AHE-50DC fan control module driver | Zev Weiss | 1 | -0/+114 | |
This device is an integrated module of the Delta AHE-50DC Open19 power shelf. I haven't been able to procure any proper documentation for it, but it seems to be a (somewhat minimally) PMBus-compliant device. It provides four fan speeds, four temperatures (three standard and one manufacturer-specific via a virtual second page), and a vin reading. Signed-off-by: Zev Weiss <zev@bewilderbeest.net> Link: https://lore.kernel.org/r/20211208213703.2577-2-zev@bewilderbeest.net Signed-off-by: Guenter Roeck <linux@roeck-us.net> |